FSU(w) Self-regulating heating cables

FSU(w) Self-regulating heating cables

Rozmiar tekstu

A

A

A

High performance self-regulating heating cables FSU(w) are designed for process temperature maintenance and protection against freezing in areas where there is high temperature maintenance or high temperature exposure.
FSU(w) The cables resist the steam flushing temperatures.

Cables are approved for use in a normal environment,
in Zone 1, 2, and in Zone 21, 22.
 

BASIC ACCESSORIES:

Terminal boxes for connection of heating cables - are used for powering, connecting and branching of heating cables.

Cable termination
Self-regulating heating cables FS+ require the use of a termination set UTK344(555)/200+.

Power output curves:
Output power for jacketed cable attached to the insulated metal pipeline at the voltage values listed below:

Type of cable
Nominal voltage 230 V AC
Power output at 10 °C (W/m)
15FSU 15
30FSU 30
45FSU 45
60FSU 60
75FSU 75
100FSU(w) 100

Certification:
FSU - SIRA 04ATEX3012
II 2G Ex e IIC T3 Gb
II 2D Ex td IIIC T200°C Db

Certification:

FSUw - SIRA 13ATEX3126

II 2G Ex e IIC T2 Gb
II 2D Ex tb IIIC T300°C Db
For information on further certification contact Generi, s.r.o.

Note:

1. Cables can also be used for other voltages, for information contact Generi staff.
2. Temperature classes are according to internationally recognized standards of authorized institutions.
3. Heating cables are approved for temperature classes using a stabilized design. This allows the use of cables in potentially explosive atmospheres without limiting thermostats. For design
of heating circuits, please contact Generi, s.r.o.
4. For additional accessories for complete installation of the heating cable and for compliance with the approval requirements, refer to the heating cable installation guide.

Size and type of the circuit breaker:
The maximum circuit lengths for the different current values of the circuit breaker are listed below. The size of the circuit breaker and the type of short-circuit protection used must be designed according to national standards. Please contact Generi, s.r.o. for design information and other supply voltages.
Short-circuit protection must be provided for each supply branch of the heating system separately.

Supply voltage 230 V AC   Max. cable length vs. size of the circuit breaker (type C circuit breaker) (m)
Type of cable Start-up temperature (°C)
10A 16A 20A 32A 50A
15FSU 10 76 122 154 172 172
0 70 112 140 172 172
-20 62 98 122 172 172
-40 52 82 102 164 172
30SFU 10 52 82 102 122 122
0 46 74 92 122 122
-20 40 66 82 122 122
-40 34 54 68 110 122
45FSU 10 38 62 76 100 100
0 34 56 70 100 100
-20 30 50 62 98 100
-40 22 34 44 70 100
60FSU 10 30 50 62 86 86
0 28 44 56 86 86
-20 20 32 40 62 86
-40 12 18 24 38 60
75FSU 10 22 34 44 70 76
0 16 26 34 54 76
-20 12 18 24 38 60
-40 8 12 14 22 36
100FSUw 10 18 30 36 58 84
0 18 28 34 56 84
-20 16 24 30 50 76
-40 14 22 28 46 70
Logo serwisu. Logo serwisu.

Kontakt

Zapraszamy do kontaktu poprzez skorzystanie z formularza kontaktowego lub telefonicznie: 535 781 557  

Formularz kontaktowy

Imię *

Nazwisko *

E-mail *

Telefon

Treść *

Do góry

Wyszukiwarka

Twoja przeglądarka internetowa, bądź system operacyjny, nie wspierają lektora w podanej wersji językowej.

Uruchom

Wstrzymaj

Przewiń animację o jedno pole w lewo.

Przewiń animację o jedno pole w prawo.

Opinie

Dziękujemy

Logo serwisu.

Ukryj moduł.